CHAPTER 2. 
INSTALLING THE SYSTEM 
The individual components of the DC Power System may be shipped as a complete 
solution factory installed and wired in an IT rack, or may be shipped separately to be 
installed in a customer provided IT rack. 
GENERAL REQUIREMENTS 
 
This product is intended only for installation in a restricted access location on or 
above a non-combustible surface. 
 
Front and rear access is required for installation. 
 
Required minimum spacing from the rear of the power and control sub-rack to a wall 
or other solid surface is thirty-six (36) inches for proper ventilation of system 
components.  Required minimum spacing from the rear of the load distribution sub-
rack to a wall or other solid surface is twelve (12) inches for proper ventilation of 
system components. 
 
See Figure 2-1 for an air flow diagram. 
 
Figure 2-1 
Air Flow Diagram 
Front
Notes:
1. Do not block
air intake openings.
A
ir
F
lo
w
Cold Aisle
Hot Aisle