IM584000300 
Installation Instructions 
Issue AB, April 3, 2013 
Spec. No. 584000300 (Model 4015-X003) 
 
Page 48 
Chapter 5. Initially Starting the System 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
 
Parameter 
Menu Navigation 
Date 
Main Menu / Settings / Controller / Date 
Time 
Main Menu / Settings / Controller / Time 
IP Communications Parameters 
(IP address, subnet mask address, 
gateway address) 
Main Menu / Settings / Communication 
Float Voltage 
Main Menu / Settings / Battery / Charge / Operating Voltage 
Equalize Voltage 
Main Menu / Settings / Battery / Charge / Batt EQ Voltage 
Battery Capacity 
Main Menu / Settings / Battery / Basic / Rated Capacity 
BTRM Feature 
Main Menu / Settings / Battery / Basic / BTRM Action 
Main Menu / Settings / Battery / Basic / BTRM Voltage 
Temperature Compensation 
Center Temperature 
Main Menu / Settings / Battery / Temp Comp / TempComp Center 
Temperature Compensation Slope 
Main Menu / Settings / Battery / Temp Comp / TempComp Coeff 
Maximum Temperature 
Compensation Voltage 
Main Menu / Settings / Battery / Temp Comp / Max TempComVolt 
High Voltage Shutdown Limit 
Main Menu / Settings / Rectifier / All Rect Set / HVSD Limit 
Over Voltage Alarm 
Main Menu / Settings / Power System / General / Over Voltage 
Under Voltage Alarm 
Main Menu / Settings / Power System / General / Under Voltage 
Table 5-1 
Basic Settings Local Menu Navigation