UPS Electrical Installation
8
Bottom Cable Entry
When making the power connections for bottom cable entry, the recommended order of pull-
ing and installing cables is to start from the bottom connections to the top connections. The 
cables must be routed around the fault braces (see Detail in Figure 9). This is to prevent the 
cables from contacting other busbars. The recommended conduit layout is shown in Figure 7.
5. For control connection details, see 2.3 - Control Cable and Communications.
6. Close and secure the interior and exterior doors.
2.3
Control Cable and Communications
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery 
system (external battery circuit breaker), communicate with a personal computer or provide alarm 
signaling to external devices or for Remote Emergency Power Off (REPO). The External Interface 
Board, arranged for this purpose, is on the rear of the operator access door.
Figure 2
External Interface Board connections layout
NOTE
For a Single Input configuration, linking busbars must be installed between the bypass and 
the rectifier input.
!
WARNING
Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning 
engineer, ensure that the system output cables are safely isolated at their termination.
!
WARNING
Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker always 
connect the circuit breaker end of the cable first.
NOTE
 If fault bracing brackets were removed during installation, they MUST be replaced.
EPO 
STATUS
TB0823
BATT 
MTR OPT
LBS 
VOLTAGE
TB0826
REPO 
FORM C
TB0824
LEPO
KEY 
STATUS
TB0825
EXTERNAL 
CAN
TB0829
INT BATT 
CAN
EXT BATT 
CAN
TB0820
INV 
CNTRL
RECT 
CNTRL
BIB
MBB
BYP 
CNTRL
ON GEN
RIB IN
TB0812
TB0813
TB0816
TB0810
ACT FILT 
STATUS
MIB
MOB
TB0811
TEMP 1
TEMP 2
BATT GND FLT
MAINT BYP 
ENABLE
ACT FILT 
CNTL
TB0821
REPO