Emerson 30-200kVA Manuel D’Utilisation

Page de 132
Installation Drawings
63
Figure 48 Cable terminal layout—60-80kVA NX
1. Main (Rectifier) connections (N1-U1-V1-W1)
2. Bypass connections (N1-U3-V3-W3)
3. Output connections (N2-U2-V2-W2)
4. Battery connections (+ / -)
5. Earth
6. Mains Input isolator (Q1)
7. Bypass Input isolator (Q2)
8. Maintenance bypass isolator (Q3)
9. Output isolator (Q5)
U1
V1
W1
N1
Batt +
Batt -
N1
U3
V3
W3
U2
V2
W2
N2
Input
Batt
Bypass
Output
NOTE
1. For split bypass operation, ensure that the busbars (*) between bypass and rectifier 
input are removed.
2. All dimensions are in millimeters.
U1
V1
W1
U3
V3
W3
N1
N2
U2
V2
W2
PE