Emerson 30-200kVA Manuel D’Utilisation

Page de 132
Operation
77
6.2
Multi Module UPS—1+N
Multi-module UPS are formed by several “single unit” UPS modules to constitute “1+N”system where 
groups of one or more, up to six, single units operate together for the purpose of providing additional 
power or reliability or both. The load is equally shared between any paralleled UPS.
Figure 64 1+N multi-module UPS with external maintenance bypass switch
Further, single unit or 1+N groups may be configured as “distributed redundant” systems with inde-
pendent outputs that nevertheless are synchronised through a Load Bus Synchroniser (LBS) so that 
critical loads can be seamlessly transferred from one system to another. See 6.3 - Modes of Opera-
tion for more information.
6.2.1
Features of NX Multi-Module UPS Configurations
1. The hardware and firmware of single module UPS units is completely compatible with the 
requirements of a multi-module system. Multi-module configuration is achieved merely through 
settings in configuration software and control cables. 
2. Parallel control cables are connected in a ring, providing both performance and redundancy. 
Dual-bus control cables are connected between any two UPS modules of each bus. The intelligent 
paralleling logic provides the user with maximum flexibility. For example, shutting down or 
starting up UPS modules in a parallel system can be done in any sequence. Transfers between 
Normal and Bypass modes of operation are synchronised and self –recovering e.g. following 
overloads and their clearance. 
3. The total load of the multi-module system can be queried from each module’s LCD. 
Distribution Cabinet 
Qout UPS2 
Qout UPS1 
Qout all UPS 
UPS3 
SUPPLIED BY OTHERS 
L1, L2, L3, N 
L1, L2, L3, N 
L1, L2, L3, N 
UPS3 OUTPUT 
UPS2 OUTPUT 
UPS1 OUTPUT 
L1, L2, L3, N 
L1, L2, L3, N 
L1, L2, L3, N
Qin Ext Byp 
Qin UPS3 
Qin UPS2 
Qin UPS1 
Q1 
Q1 
CHARGER 
UPS2 
INPUT MAINS SUPPLY 
BYPASS MAINS SUPPLY 
L1, L2, L3, N 
L1, L2, L3, N 
INPUT MAINS SUPPLY 
BYPASS MAINS SUPPLY 
L1, L2, L3, N 
INPUT MAINS SUPPLY 
RECTIFER 
INVERTER 
Q5 
Q3 
Q2 
Qout UPS3 
Qout 
BYP 
CHARGER 
RECTIFER 
INVERTER 
Q5 
Q3 
Q2 
UPS1 
Q1 
CHARGER 
RECTIFER 
INVERTER 
Q5 
Q3 
Q2