Options—For Assembly Inside the UPS Cabinet
112
9.2.2
Relay Card
The Relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, 
the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay 
contact monitoring systems.
The Relay card is rated for 24 VAC/VDC at 1A and supported in any of the three NX Intellislot bays.
**A Summary Alarm occurs when any of the following conditions exist:
• Utility power is out of the acceptable range (voltage and/or frequency)
• UPS is in BYPASS MODE (load not on Inverter power)
• UPS Battery is LOW
• UPS fault has occurred
Table 28
Relay Card pin configuration
Pin
Function Operation
1
UPS Fault
Closed if no UPS failure
2-3
Not Used
4
UPS Fault
Closed if UPS fails
5
Summary Alarm**
Closed if SUMMARY ALARM** occurs
6
Summary Alarm**
Closed if no alarm conditions are present
7
 Any Mode Shutdown return
Not – use External EPO terminal
8
Not Used
9
Common - Low Battery
10
Low Battery
Closed if battery is OK
11
Low Battery
Closed if LOW BATTERY point occurs.
12-13
Not Used
14
UPS Any Mode Shutdown
Not support– use External EPO terminal
15
On UPS
Closed if ON UPS (inverter) power
16
On Battery
Closed if ON BATTERY power (Utility failure)
17
Common - UPS Fault, Summary Alarm,
On UPS, On Battery, On Bypass
18
On Battery
Closed if not ON Battery power (Utility OK)
19 
÷ 23
Not Used
24
On Bypass
Closed if ON BYPASS
25
Not Used
Table 29: 
#
Connection
Description
JP01
Pin 9 to Pin 17 
Allows all relay COMMONS to be tied together.
JP02
Pin 7 to Pin 17
REMOVE
 - (Interconnects all relay COMMONS and the (not supported) 
ANY MODE SHUTDOWN Return.