Technical Specifications
116
Table 34
Efficiency, AC/AC
Input and output voltage 400VAC, battery charged, full rated linear load
Rated Power, kVA
Unit of
Measurement
30
40
60
80
100
120
140
160
200
Normal Mode
(dual conversion)
%
89
90
91
91
90.6
91.1
92.5
92.7
92.8
ECO Mode
%
94
94.8
94.3
95
95
95.6
95.5
95.7
95.7
Inverter Efficiency (DC/AC) (battery at nominal voltage 480VDC and full-rated linear load)
Battery Mode
%
93
93
94
94
94
94
94
94
94
Heat Losses & Air Exchange—Ventilation
Normal Mode
kW
3.0
3.6
4.7
6.3
7.9
9.5
10.8
11.8
14.5
ECO Mode
kW
1.5
1.6
2.0
2.6
3.5
4.3
7.0
7.6
9.9
No Load
kW
1.3
1.4
1.9
2.4
3.0
3.7
4.9
4.9
5.6
Forced air cooling
(front intake, top exhaust)
L/sec
333
333
458
458
500
500
671
671
721
M
3
/hr
1200
1650
1800
2415
2595
Table 35
Mechanical characteristics
Rated Power, kVA
Unit of
Measurement
30
40
60
80
100
120
140
160
200
Dimensions, H x W x D
mm (in)
1600 x 600 x 825
(63 x 23.6 x 32.5)
1800 x 700 x 825
(70.8 x 27.5 x 32.5)
1800 x 1000 x 825
(70.8 x 39.4 x 32.5)
Mass, without batteries
kg (lb)
312
(688)
341
(752)
401
(884)
445
(981)
720
(1587)
720
(1587)
960
(2116)
960
(2116)
1060
(2337)
Finish
Colour
Pantone 877 (Silver grey) 
eqvl Becker Silver epoxy polyester powder 041-37-2
Protection Degree
IEC 60529
IP20
(finger-proof with front doors open or closed)
Values listed are the mass of the units with options added (ground fault sensor, bypass share inductors and redundant fans).
Table 36
Rectifier AC input (mains)
Rated power, kVA
Unit of
Measurement
30
40
60
80
100
120
140
160
200
Rated AC Input Voltage
1
VAC
380/400/415 V
(three-phase and sharing neutral with the bypass input)
Input voltage tolerance
2
VAC
305V to 477V 304V to 208V (output de-rated from 99% to 70%)
Frequency
1
Hz
50/60Hz (tolerance 40Hz to 72Hz)
Power Factor
full load
kW/kVA
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.99
half load
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Input power
rated
3
kVA
27.2
35.9
53.3
71.0
88.8
107
122
139
174
maximum
4
32.9
43.0
64.6
85.2
107
128
159
182
228
Input current
rated
3
A
39
52
77
103
128
154
177
201
252
maximum
4
48
62
93
123
154
185
231
264
330
Harmonic Current Distort (with 
linear or non-linear balanced 
load and at input THVD
 2%)
THID
% FL
3
3
3
3
3
3
3.5
3
3
Duration of progressive power 
walk-in 
sec
10 seconds to reach full rated current
(selectable 5 through 30 seconds in 5 second intervals)
1.
Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.
2.
At 305V input mains, the UPS maintains the specified output voltage at rated load without discharging a previously charged battery.
3.
EN 50091-3: at rated load and input voltage 400V, battery charged
4.
EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.