Emerson 208V Manuel D’Utilisation

Page de 48
Specifications
36
Table 12
Specifications of GXT3-1500RT120 - GXT3-3000RT120 and GXT3-3000RT208 UPS
Parameters
Product Model
GXT3-1500RT120
(1500VA/1350W)
GXT3-2000RT120
(2000VA/1800W)
GXT3-3000RT120
(3000VA/2700W)
GXT3-3000RT208
(3000VA/2700W)
Dimensions, D × W × H, in. (mm)
Unit
19.7 x 16.9 x 3.4
(497 × 430 × 85)
23.7 x 16.9 x 3.4
(602 × 430 × 85)
Shipping
25.5 x 23.9 x 10.6
(647 x 607 x 270)
29.4 x 23.4 x 10.6
(747 x 607 x 270)
Weight, lb. (kg)
Unit
51.1 (23.2)
56.1 (25.5)
71.4 (32.4)
Shipping
57.3 (26)
61.7 (28)
77 (35)
Input AC
Voltage Range (typical)
120VAC nominal; variable based on output load
208VAC nominal; 
variable
based on output load
90 - 100% loading
102VAC/140VAC
177VAC/280VAC
70 - 90% loading
96VAC/140VAC
168VAC/280VAC
30 - 70% loading
84VAC/140VAC
150VAC/280VAC
0 - 30% loading
60VAC/140VAC
115VAC/280VAC
Frequency
40 - 70Hz; Auto Sensing
Input Power Cord
10 ft. attached w/
NEMA 5-15P plug
10 ft. attached w/
NEMA 5-20P plug
10 ft. attached w/
NEMA L5-30P plug
10 ft. attached w/
NEMA L6-20P plug
Output AC
Output Receptacles
5-15R × 6
5-20R × 6
L5-30R×1+5-20R×6 L6-20R×1+L6-15R×2
Voltage
110/115/120VAC (user-configurable); ±3%
208/220/230/240 VAC
(user-configurable); ±3%
Waveform
Sine wave
Utility (AC) Mode Overload
200% for 2 seconds
150% for 50 seconds
200% for 2 seconds
150% for 10 seconds
Battery
Type
Valve-regulated, nonspillable, lead acid
Qty×V×Rating
4 × 12V × 7.2Ah
4 × 12V × 9.0Ah
6 × 12V × 9.0Ah
6 × 12V × 9.0Ah
Battery Mfr./Part # Panasonic/UP-RW1236
CSB/GP 1272
Panasonic/UP- RW1245; CSB/HR 1234W F2
Backup Time
See Table 15
Recharge Time
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)
Environmental
Operating Temperature, °F (°C)
+32 to +104 (0 to 40); see Table 14 - Operating temperature parameters
Storage Temperature, °F (°C)
5 to +122 (-15 to 50)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Storage Elevation
50,000 ft. (15000m) maximum
Audible Noise
< 45dBA at 3ft (1m) rear
< 46 dBA at 3ft. (1m)
front and side
 <48dBA max @ 3ft (1m) front and side
<48dBA max @ 3ft. (1m) rear
Agency
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Part 15, Class A=CISPR22 Class B
Surge Immunity
IEC 62040-2 2nd Ed
Transportation
ISTA Procedure 1A