The two diagrams below show input wiring circuits using an external supply. If using the 
upper wiring diagram, be sure to use a diode with the external supply. This will prevent a 
power supply contention in case the SR/SK switch is accidentally placed in the incorrect 
position. Be sure to use the correct SR/SK switch position shown for each wiring 
diagram.
L200
2
L
24V

SK
SR
SK
SR
PCS
Input 
circuits
1
5
Logic GND
1
5
GND
Open collector outputs, 
NPN transistors
Input 
switches
Sinking Inputs, External Supply
SR/SK switch = SK position
Field device
L200
2
L
24V

SK
SR
SK
SR
PCS
Input 
circuits
1
5
1
5
GND
PNP transistor
sourcing outputs
Input 
switches
Sourcing Inputs, External Supply
SR/SK switch = SR position
Field device
Logic GND
24V


+V
*
*
* Note: If the external power supply GND is (optionally) 
connected to [L], then install the above diode.
24V