Siemens 440 Manuel D’Utilisation

Page de 78
6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
36 
Operating Instructions (Compact) 
6.4.4 
Digital outputs (DOUT) 
 
 
BI: Function of digital output 1 * 
Defines source of digital output 1. 
 
BI: Function of digital output 2 * 
Defines source of digital output 2.
 
 
BI: Function of digital output 3 * 
Defines source of digital output 3.
 
 
CO/BO: State of digital outputs 
Displays status of digital outputs (also 
includes inversion of digital outputs via 
P0748). 
 
Invert digital output 
Defines high and low states of relay for a 
given function. 
Common Settings: 
Closed 
52.0 Drive 
ready 
52.1 
Drive ready to run 
52.2 Drive 
running 
52.3  Drive fault active 
52.4 OFF2 
active 
52.5 OFF3 
active 
52.6  Switch on inhibit active 
52.7 Drive 
warning 
active 
52.8  Deviation setpoint/actual value 
52.9  PZD control (Process Data Control)  0 
52.A  Maximum frequency reached 
52.B  Warning: Motor current limit 
52.C  Motor holding brake (MHB) active 
52.D Motor 
overload 
52.E  Motor running direction right 
52.F Inverter 
overload 
53.0  DC brake active 
53.1  Act. freq. f_act > P2167 (f_off) 
53.2  Act. freq. f_act <= P1080 (f_min) 
53.3  Act. current r0027 > P2170 
53.4  Act. freq. f_act > P2155 (f_1) 
53.5  Act. freq. f_act <= P2155 (f_1) 
53.6  Act. freq. f_act >= setpoint 
53.7  Act. Vdc r0026 < P2172 
53.8  Act. Vdc r0026 > P2172 
53.A  PID output  
 
 
r2294 == P2292 (PID_min) 
53.B  PID output  
 
 
r2294 == P2291 (PID_max) 
0 
 
(52:3)
BI: Fct. of DOUT 1
P0731.C
-1
0
1
Invert DOUTs
0 ... 7
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.20
Kl.18
.0
Function
xxxx.y
rxxxx.y
P0731 = xxxx.y
DOUT channel
Relay :
DC 30 V / 5 A
AC 250 V / 2 A
Kl.28
Kl.9
int. 24 V
max. 100 mA
NO
COM
NC
Kl.19
or
Text
max. opening / closing time
5 / 10 ms
 
 
52.3
0
 
P0731 = ... 
52.7
 
0.0
 
P0748 = ... 
P0733 = ... 
P0732 = ... 
r0747 = ...