Siemens CM220/3 Manuel D’Utilisation

Page de 40
English
2.  Installation
© STÖBER plc 1998
05.02.01
6
2.3  Electrical Installation
Remove the four M5 cross-head screws on the inverter's cover to access the electrical terminals (see Figure 3
and Figure 4)
.
Notes:
(1)
Refer to the electrical data table for cable sizes (see section 6).
(2)
We recommend introducing a `drip loop' when connecting the mains and control cables (see
Figure 5)
.
CAUTION
The printed circuit boards contain CMOS components that are particularly sensitive to static
electricity. For this reason, avoid touching the boards or components with your hands or metal
objects.
Note: Jumper in ‘V’ position = voltage input (default)
Jumper in ‘I’ position = current input
Ensure that the following tightening torques are used:
Electrical terminal screws:
1.1 Nm
Access cover retaining screws:
4.0 Nm
Gland hole covers:
1.0 Nm
IMPORTANT
V
I
JP303
JP302
JP303
Jumpers for
PI Input Type
Default = V
V
I
JP303
JP300
JP301
Jumpers for
Analogue Input Type
Default = V
Mains Connector *
LED
(Green)
LED
(Yellow)
Control Cable Connector
(PL800)
1
12
1
4
OPm2 Connector
(SK200)
Control
Potentiometer
(R314)
L1  L2  L3
-
+
*
Check that the supply voltage is correct for the
COMBIMASTER used by referring to the voltage
code part of the order number (see section 6).
Figure 1:  Electrical Connection Diagram