Emergency supply period 
shorter than nominal value. 
Batteries not fully charged 
/ batteries old resp. defect
Charge the batteries for 
at least for the charging 
time acc. Chapter 2.3, 
and then check 
capacity. If the problem 
still persists, consult 
your dealer. 
LED “Line” and LED “Fault” 
light up, continous tone 
(Error No. 17). 
Cutoff because of UPS 
internal overtemperature 
detection. 
Check that no overload 
is present, that the 
UPS vent is not 
blocked and that the 
environment 
temperature lies in the 
tolerance. Await 10 
min. cooling phase, 
then switch on again.   
Error No. 19 
Cutoff because of short 
circuit in UPS output. 
Switch off the UPS and 
all loads. Remove short 
circuit. Switch on UPS 
again, connect loads 
one by one. 
LED “Fault” lights, LED 
“Bat.” blinks, warning tone 
once a second. 
Charger or Batteries 
damaged. 
Notify dealer! 
LED “Fault” lights up, 
permanent warning tone. 
UPS fault. 
Notify dealer! 
Further diagnosis can be found also in the table under 
chapter 8.1.1.  
If you cannot solve the problem that has occurred, stop the 
entire procedure, switch off the UPS and disconnect the 
connector from the socket. Please contact our hotline in this 
case (see page 5). 
Please have the serial number of the unit as well as the 
purchase date to hand in this case. The hotline will provide 
you with technical support and can inform you about further 
procedures once you have described the problem.