6.1.1  Connecting the internal battery 
Fig. 13
 
: Opening the front panel of the UPS 
1.  Make sure that the UPS is not electrically charged and not 
connected to a power source. 
First unscrew the two centered screws in front panel (1) 
using a suitable cross-slot screwdriver (recommended: 
Phillips PH1). 
2.  Now reach behind the front panel on the right and the left 
and pull the UPS approx. 70 mm forward out of the rack (2) 
so that the silver sticker on the top of the UPS with the safety 
precautions becomes visible. 
3.  Now slide the front panel a few millimeters sideways to the 
left (3). The lock will be released … 
4.  … and you can rotate the entire front panel upwards (4). 
Make sure not to cut the flexible ribbon cable to the LCD 
display!   
Do not use excessive force. 
5.  Now connect the internal battery system by connecting the 
two battery connectors (each consisting of a red and a black 
connector) with each other: red in red, black in black (also see 
following Fig. 14). 
this part stays  
in the rack!