Micro Technic PV-5127 Manuel D’Utilisation

Page de 31
Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 21 of 31 
mounted directly on the battery.  The charging is disabled when the temperature according to this 
sensor rises above 55°C, and enabled when it falls below 45°C.  The J1 input has the following 
function: 
 
Installed on J1 
Charger function 
Nothing 
Disabled.  See note. 
A jumper 
Enabled (factory default) 
A KTY11-5 sensor 
Enabled when not too hot 
 
Note: When using the PV-5127 with a PV-1075 NiMH battery module, you must disable the PV-
5127 charger by leaving J1 unconnected. 
 
You can connect a Battery LED to the CN2 connector.  The LED shows these statuses: 
 
Battery LED  Meaning 
Off 
Battery voltage OK (
medium
 or 
full
).  If mains is present and the charger is enabled, 
the charger is in 
trickle charge
 mode, otherwise it is 
off
Flashing 
Charger is in 
fast charge
 mode. 
Steady on 
Battery error.  This indicates that the battery is either 
empty
low
, or 
disconnected
 