Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
Table A--1. Ratings & External Wiring Requirements for
Powerware 9315
MBM 30---160
kVA
, 480:208
VAC
/600:208
VAC
Rating and External Wiring Requirement
Units
Rating 60 Hz
Basic unit rating at
0.8 lagging PF load
KVA
KW
160
128
130
104
100
80
80
64
UPS Input Voltage/Bypass Input
UPS Output Voltage
VOLTS
VOLTS
480
208
600
208
480
208
600
208
408
208
600
208
480
208
600
208
A
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
96
77
A
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
B
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
96
77
B
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
C
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
444
361
361
278
278
222
222
C
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
D
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
444
361
361
278
278
222
222
D
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
E
Control Wiring to UPS
(2) Conductors
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
Basic unit rating at
0.8 lagging PF load
KVA
KW
65
52
50
40
40
32
30
24
UPS Input Voltage/Bypass Input
UPS Output Voltage
VOLTS
VOLTS
480
208
600
208
480
208
600
208
480
208
600
208
480
208
600
208
A
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
78
63
60
48
48
38
36
29
A
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
B
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
78
63
60
48
48
38
36
29
B
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
C
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
180
180
139
139
111
111
83
83
C
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
D
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
180
180
139
139
111
111
83
83
D
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
E
Control Wiring to UPS
(2) Conductors
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
Note:
Callout letters
A, B, C, D,
and
E
map to drawing 164201177---5 (Reverse Transfer Connection) and
164201177---8 (Parallel Connection). Read and understand the notes on drawings when planning your installation.