Standard Series Specifications
4.0
Specifications
MODEL NUMBER
UE1E1E008-5M
UE1E1E010-5M
CAPACITY
800 VA  (0.56 kW)
1000 VA (0.7 kW)
Input
Input voltage
Single phase, 220 Vac, +10% to -30% (*)
Input  frequency
45 to 65 Hz
Input capacity
800 VA
1000 VA
Input power factor
Approximate unity (0.95 to 1.0)
Battery
Battery rated voltage
60 Vdc
         Battery backup time when fully charged    8 min. at full load (**)
7 min. at full load (**)
             with 0.7 power factor at 77
°
 F (25
°
 C)    20 min. at half load (**)
18 min. at half load (**)
 Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output
Output voltage
Single-phase, 220 volts
Output voltage regulation
Within +/- 3%, steady state
 Output frequency
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor
0.7 lagging (0.6 to 1.0)
Voltage transient characteristic
+/- 8% under 100% load step change
Rated output current (rms)
3.6A
4.5A
Maximum output current (peak)
10.8A
13.5A
Inverter  overload  capacity
150% for 30 seconds
Crest factor
3.0
Environment
Operating  temperature
32 to 104
°
 F (0 to 40
°
 C), optimal  at 77
°
 F (25
°
 C)
Storage  temperature
-4 to 104
°
 F (-20 to 40
°
 C)
Operating  humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
External dimensions
8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
58.8 lb (26.7 kg)
60.7 lb (27.5 kg)
Acoustical noise
50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
85%
87%
Switches
Bypass switch
Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs  (transfer time is
approximately 4 msec)
Interfaces
 IBM 
(TM) 
AS/400
LAN Manager
See section 6.0 for details.
 Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computer shutdown
Contact Toshiba for details on this option
External  battery  pack
Contact Toshiba for details on this option
(*)  Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**)  Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.