G8000 Series Installation and Operation Manual
The UPS battery cabinet and bypass breaker should be wired as shown below in Figure 11.15.  
FIGURE 11.15 - CONNECTION BETWEEN UPS, BATTERY CABINET & BYPASS BREAKER
11.7    Grounding Configuration
This section describes the grounding configuration to be used with various AC service entrance configurations.
Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral line 
must be made appropriately according to the system configuration.
11.7.1    Recommended configuration (for 4 wire input with Input Neutral 
grounded)
Figure 11.16 shows recommended grounding configuration when the input neutral is grounded.
The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be 
disconnected from the ground bus. The neutral connection for the UPS bypass input should be grounded.
10
11
12
13
14
15
16
17
18
19
20
21
22
TC
TB1
Battery Cabinet
Overheat  
B-Contact
Bypass Breaker
Ext. EPO (Customer) N.O. Contacts
UPS Cabinet
Jumper wire if battery 
OH is not applied
To Bypass 
Input
To DC 
Input
Power Source  
for trip coil
Power Source
Auxillary A-
contact