12    UPS Specifications
12.1    Specification Table
G8000 Specifications
Model Number
T80S3K08
KK6XSxx
T80S3K10
KK6XSxx
T80S3K12
KK6XSxx
T80S3K15 
KK6Xxx
T80S3K22 
KK6XSxx
T80S3K30 
KK6XSxx
T80S3K50 
KK6XSxx
Input
Rated Output 
Capacity
80 kVA /  
80 kW
100 kVA /   
100 kW
125 kVA /   
100 kW
150 kVA /  
150 kW
225 kVA /  
225 kW
300 kVA /  
300 kW
500 kVA /  
450 kW
Voltage
480 VAC (+10% to -15%)
Frequency
60 Hz (+/-5%)
Configuration
3 Phase; 3 Wire + GND
Input kVA
Normal (Charging)
89 kVA 
(100 kVA)
111 kVA 
(122 kVA)
112 kVA 
(123 kVA)
163 kVA 
(174 kVA)
247 kVA 
(258 kVA)
329 kVA 
(340 kVA)
484 kVA 
(505 kVA)
Power Factor
> 0.99 PF Lagging
Walk-in Function
EEPROM Upgrade
Maximum Input 
Current
Normal (Charging)
107 A 
(120 A)
134 A 
(147 A)
135 A 
(148 A)
196 A 
(209 A)
297 A 
(311 A)
396 A 
(409 A)
582 A
(608 A)
Reflected THD
< 5% @ 100% Load
< 6% @ 25% Load
Bypass
Configuration
3-Phase; 4-Wire + Gnd
Voltage
480/277V (±10%)
Frequency
60 Hz (+/-5%)
Bypass Overload 
Capacity
1000% for 1 Cycle, 500% for 2 Cycle
Battery
Number of Cells
180
240
Type
Lead Acid (Contact factory for alternative options)
DC Nominal
360V
480V
DC Minimum
288V
408V
Float Charge
405V
540V
Ripple Current 
(without batteries)
AC Ripple on DC Bus:  < 0.2% of DC Voltage
Back-up Time
Application Specific
Max DC Charging 
Current 
30 A
30 A
30 A
30 A
30 A
30 A
45 A
Max Discharge
292 A
359 A
365 A
533 A
805 A
1073 A
1193 A
Battery Capacity 
Required for Full 
Load Output
88 kWB
108 kWB
110 kWB
160 kWB
242 kWB
323 kWB
478 kWB