Transition Networks SPS-48V Manuel D’Utilisation

Page de 4
TECHNICAL SPECIFICATIONS
Input
Input Voltage
48 VDC
Inrush Current
0.20 A (peak cold start)
Hold-Up Time
20 msec minimum at full load and nominal input
voltage
Isolation Voltage
(Dielectric withstand) Meets IEC 960 for one minute.
1,500 VAC: 
Output/Input
500 VAC:
Input/Safety GND
500 VAC:
Output/Safety GND
Output
Output Voltage
12 VDC
Output Current
0.8 A
Line Regulation
±0.5 % of all output within specified range
Load Regulation
±1.0 % at 20 % load to full-rated load
Cross Regulation
±1.0 % maximum on any output change from 50 % to
100 % rated load
Transient Response
Output voltage returns in less than 3 msec following a
50 % load change
Over Load Protection
(OLP) When the average power rating exceeds 125%-
150% of maximum power, output voltages reduced to
a safe dissipation level; protects against short circuit of
any output.
Over Voltage Protection (OVP) 124 % ±8 % on output.  
Over Circuit Protection Withstands a continous short without damage; returns
automatically to regulation upon removal of short.
No Load Operation
No damage to power supply when operating at no
load. 
Overshoot Protection
No voltage spike at power-on, power-off, or power
failure.
4.
Connect +48-VDC terminal to 48-to-12 VDC External Power Supply
terminal block control marked “+”. Turn terminal screw clockwise to
secure.
5.
Connect -48-VDC terminal to 48-to-12 VDC External Power Supply
terminal block control marked “-”. Turn terminal screw clockwise to
secure.
6.
Connect ground terminal to 48-to-12 VDC External Power Supply
terminal block control marked “chassis ground”. Turn terminal screw
clockwise to secure.
7.
Ensure that external power source is powered ON.
GND
-
+