ADC Power Distribution Manuel D’Utilisation

Page de 40
ADCP-80-575 • Issue 2 • December 2006
Page 12
© 2006, ADC Telecommunications, Inc.
1.18 Voltage Designation Label
A voltage designation label, shown in 
, is provided with the fuse platform. The label
may be filled out with the actual voltage present on the buses and placed on the fuse platform.
The voltage designation label has a pressure sensitive adhesive backing for attachment.
Figure 5. Voltage Designation Label
1.19 Environmental Characteristics
 lists the environmental characteristics of the fuse platform.
1.20 Material and Finish
The fuse platform chassis and brackets are made of 16 gauge cold rolled steel. The fuse
platform and brackets are finished with powder paint that is putty white color.
1.21 Cooling
Vent openings are provided in the top and bottom of the fuse platform. The vent openings allow
convection cooling of all components without the use of fans or blowers. A minimum of 1.75
Table 2. Fuse Platform Environmental Characteristics
PARAMETER
DESCRIPTION
Operating temperature
–5° C to +50° C
Storage temperature
–45° C to +85° C
Humidity range (operating)
0% to 95% humidity (non-condensing)
Altitude range
–197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire rating
All components UL94-V1
Earthquake design
NEBS Level 3; Zone 4
Acoustic noise
0 dBA above ambient
Heat dissipation (fully loaded)
80 watts maximum per fuse platform @ 100 Amps (40 
watts maximum per bus @ 100 Amps)
Heat dissipation (no load)
1 watt per bus
0.38 IN.
(0.96 CM)
1.00 IN.
(2.54 CM)
14228-A