APC AP89XX Manuel D’Utilisation

Page de 128
Switched Rack PDU User Guide
91
Administration: Notification
Event Actions 
Path: Administration > Notification > Event Actions > options
Types of notification
You can configure event actions to occur in response to an event or group of events. These actions notify 
users of the event in any of several ways:
•  Active, automatic notification. The specified users or monitoring devices are contacted directly.
– E-mail notification
– SNMP traps
– APC Remote Monitoring Service
– Syslog notification
•  Indirect notification 
– Event log. If no direct notification is configured, users must check the log to determine which 
events have occurred
– Queries (SNMP GETs)
For more information, see “SNMP” on page 87. SNMP enables an NMS to perform 
informational queries. For SNMPv1, which does not encrypt data before transmission, 
configuring the most restrictive SNMP access type (READ) enables informational queries 
without the risk of allowing remote configuration changes.
Configure event actions
Notification parameters. 
For events that have an associated clearing event, you can also set the 
following parameters as you configure events individually or by group, as described in the next two 
sections. To access the parameters, click the receiver or recipient name.
Parameter
Description
Delay x time before 
sending
If the event persists for the specified time, a notification is sent. If the condition clears 
before the time expires, no notification is sent.
Repeat at an interval 
of x time
The notification is sent at the specified interval (e.g., every 2 minutes).
Up to x times
During an active event, the notification repeats for this number of times.
Until condition 
clears
The notification is sent repeatedly until the condition clears or is resolved.