Switched Rack PDU User Guide
phNearOver
Access: 
Administrator, Device User
Description: 
Set or view the phase near-overload threshold in kilowatts. To specify phases, choose 
from the following options. Type: 
all
, a single phase, a range, or a comma-separated list of phases.
Example 1: 
To set the near-overload threshold for all phases to 10 kW, type:
apc> phNearOver all 10
E000: Success
Example 2: 
To view the near-overload threshold for phases 1 through 3, type:
apc> phNearOver 1-3
E000: Success
1: 10 A
2: 10 A
3: 10 A
phOverLoad
Access: 
Administrator, Device User
Description: 
Set or view the phase overload threshold in kilowatts. To specify phases, choose from the 
following options. Type: 
all
, a single phase, a range, or a comma-separated list of phases.
Example 1: 
To set the overload threshold for all phases to 13 kW, type:
apc> phOverLoad all 13
E000: Success
Example 2: 
To view the overload threshold for phases 1 through 3, type:
apc> phOverLoad 1-3
E000: Success
1: 13 A
2: 13 A
3: 13 A