APC AP89XX Manuel D’Utilisation

Page de 128
68
Switched Rack PDU User Guide
Configure outlet settings and the outlet name
The following settings are available:
To configure outlet settings or outlet names, select the Device Manager tab and then Configuration 
from the left navigation menu. Click the Configure Multiple Outlets button in the Outlet 
Configuration
 section or click the outlet name.
•  Configure outlet settings for multiple outlets:
– Select the checkboxes next to the numbers of the outlets you want to modify, or select the All 
Outlets checkbox.
– Enter values for Name and Link, and click the Apply button immediately below the list.
– Enter values for Power On DelayPower Off Delay, or Reboot Duration, and click the 
Apply button immediately below the list.
•  Configure outlet settings for a single outlet:
– Enter values for Name and Link, and click the Apply button immediately below the list.
– Enter values for Power On DelayPower Off Delay, or Reboot Duration, and click the 
Apply button immediately below the list.
Setting
Description
Name
Set the name for one or more outlets. The name is displayed next to the outlet 
number on status screens.
External Link
Define an HTTP or HTTPS link to a Web site or IP address.
• http://www.apc.com links the outlet to the home page of the APC Web site.
 
• http://pdu_ip_address, where pdu_ip_address is the IP address of the Rack 
PDU and links the outlet to the Web interface of the Rack PDU at the IP 
address, enabling authorized users to log on.
Power On Delay
Set the number of seconds that the Rack PDU waits after a command is issued 
before applying power to an outlet.
Note:To configure an outlet to remain off at all times, select the Never radio 
button next to Power On Delay
Power Off Delay
Set the number of seconds that the Rack PDU waits after a command is issued 
before removing power from an outlet.
Note:To configure an outlet to remain on at all times, select the Never radio but-
ton next to Power Off Delay
Reboot Duration
Set the number of seconds an outlet remains off before restarting.