Switched Rack PDU User Guide
RADIUS and Network Port Sharing
Note: See the  Security Handbook for APC Network Management Cards for more information on using 
RADIUS.
For RADIUS users file with VSAs, outlets on guest Rack PDUs can be associated to RADIUS users by 
using the following method. 
# give user access to outlets 1, 2, and 3 on unit 1,
# outlet 7 on unit 2, outlets 1 through 6
# on unit 3, and outlets 1,2,4 through 6, 7 through 10,
# and 20 on unit 4
newOutletUser Auth-Type = Local, User-Password = "newoutlets"
APC-Service-Type = Outlet,
APC-Outlets = "1[1,2,3];2[7];3[1-6];4[1,2,4-6,7-10,20];"
Inactivity Timeout 
Path: Administration > Security > Auto Log Off
Use this option to configure the time (3 minutes by default) that the system waits before logging off an 
inactive user. If you change this value, you must log off for the change to take effect.
Note: This timer continues to run if a user closes the browser window without first logging off by 
clicking Log Off
 
at the upper right. Because that user is still considered to be logged on, no user can log 
on until the time specified as Minutes of Inactivity
 
expires. For example, with the default value for 
Minutes of Inactivity, if a user closes the browser window without logging off, no user can log on for 3 
minutes.