de-energize. For the first 5 minutes, CB will not accept a signal from F/S. This minimum 
5-minute freeze time is short cycle protection for Comp. At the end of 5 minutes, F/S 
assumes control. As ice builds on the evaporator, the water level in the tank lowers. The 
freeze cycle continues until F/S opens and terminates the cycle. There is a 15 second 
delay before CB acknowledges an open F/S. 
d) Pump-Out Cycle 
LEDs 1, 3, and  are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on. 
CAUTION! Do not adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this 
position on this model prevents the unit from operating correctly and may cause 
damage.
 For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." Comp and 
FMR remain energized, HGV energizes, WV energizes if S4 dip switch 3 off and 4 on. 
LLV and FM de-energize. PM stops for  seconds then reverses, taking water from the 
bottom of the tank and forcing pressure against the check valve seat allowing water to 
go through the check valve and down the drain. At the same time, water flows through 
the small tube to power flush F/S. When the pump-out timer expires, the pump-out is 
complete.
The first pump-out occurs after the 11th freeze cycle, then every 10th cycle thereafter. 
The pump-out frequency control is factory set, and generally no adjustment is required. 
However, where water quality is bad and the icemaker needs a pump-out more often, the 
pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 & 
6) can be set to have a pump-out occur every cycle, or every , 5, or 10 cycles. Timing of 
the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below. For 
details, see "II.C.3.d) Pump-Out Frequency Control (S4 dip switch 5 & 6)."
S4 Dip Switch Setting
Pump-Out 
Frequency
1st Pump-Out
No. 5
No. 6
OFF
OFF
Every cycle
After nd freeze cycle
ON
OFF
Every  cycles
After 3rd freeze cycle
OFF
ON
Every 5 cycles
After 6th freeze cycle
ON
ON
Every 10 cycles
After 11th freeze cycle
e) Harvest Cycle 
Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."
Note: Unit continues to cycle until BC is satisfied or power is turned off. The unit always 
restarts at the 1-minute fill cycle.
f) Shutdown
When ice contacts the thermostatic bulb (BC switch open), BC shuts down the unit within 
10 seconds. The bin control is factory set, and generally no adjustment is required. 
However, adjustment may be needed in some conditions, particularly at higher altitude 
locations.
Legend: 
BC–bin control; CB–control board; Comp–compressor; FMR–fan motor-remote; 
FM–fan motor; F/S–float switch; HGV–hot gas valve; LLV–liquid line valve;      
PM–pump motor; WV–inlet water valve