2. Features
a) Maximum Water Supply Period - 6 minutes
The inlet water valve will be open during harvest for 6 minutes or the length of harvest 
minus 0 or 50 seconds (harvest pump timer (S4 dip switch 7)), whichever is shorter. For 
details, see "II.C.3.e) Harvest Pump Timer (S4 dip switch 7)."
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest 
cycle takes more than 0 minutes to complete. The control board will signal this problem 
using  beeps every 3 seconds.
The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle 
takes longer than the time specified to complete. The control board will signal this 
problem using 3 beeps every 3 seconds. The freeze timer is factory set using S4 dip 
switch 9 & 10. For details, see "II.C.3.g) Freeze Timer (S4 dip switch 9 & 10). 
The "ALARM RESET" button on the control board must be pressed with power on to 
reset either of these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high 
temperature safety. This protects the unit from excessively high temperatures. If the 
evaporator temperature reaches 17°F±7°F (53°C±4°C), the control board reads a .8 kΩ 
signal from the thermistor and shuts down the icemaker. 
The control board will signal this problem using 1 beep every 3 seconds. The "ALARM 
RESET" button on the control board must be pressed with power on to reset the safety.
d) Low Water Safety
The control board checks the position of the float switch at the end of the initial 1-minute 
fill cycle and at the end of each harvest cycle. If the float switch is in the up position 
(electrical circuit closed), the control board changes to the next cycle. If the float switch 
is in the down position (electrical circuit open), the control board changes to additional 
1-minute fill cycles until water enters the tank and closes the float switch. When the float 
switch closes, the control board changes to the next cycle. The unit will not start without 
adequate water in the tank. This serves as a low water safety to protect the water pump.
For water-cooled model, if the condenser water supply is shut off, the unit is protected by 
the high-pressure switch.
e) High Voltage and Low Voltage Cut-outs
The maximum and minimum allowable supply voltages of this icemaker are limited by 
the high voltage and low voltage cut-outs. If miswiring (especially on single phase 3 wire 
models) causes excessive voltage (147Vac±5% or more), the high voltage cut-out shuts 
down the circuit in 3 seconds and the icemaker automatically stops. The control board 
will signal this problem using 7 beeps every 3 seconds.
The icemaker also automatically stops in cases of insufficient voltage (9Vac±5% or 
less). The control board will signal this problem using 6 beeps every 3 seconds.
When the proper supply voltage is resumed, the icemaker automatically starts running 
again.