V. Removal and Replacement of Components
 WARNING
1. This unit should be diagnosed and repaired only by qualified service 
personnel to reduce the risk of death, electric shock, serious injury, or fire.
. Move the control switch to the "OFF" position and turn off the power supply 
before servicing. 
3. 
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews 
are securely in place after the unit is serviced. Make sure that none have 
fallen into the storage bin.
4. Make sure all food zones in the icemaker and storage bin are clean after 
the unit is serviced. For cleaning procedures, see "VI. Cleaning and 
Maintenance."
A. Service for Refrigerant Lines
 WARNING
1. Repairs requiring the refrigeration circuit to be opened must be performed by 
properly trained and EPA-certified service personnel.
. Always recover the refrigerant and store it in an approved container. Do not 
discharge the refrigerant into the atmosphere.
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a 
trace of refrigerant to the system (if using an electronic leak detector), and 
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A 
as a mixture with pressurized air for leak testing. 
CAUTION
1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture 
quickly. Therefore it is important to prevent moisture from entering the 
system when replacing or servicing parts.
. Always install a new drier every time the sealed refrigeration system is 
opened. 
3. Do not replace the drier until after all other repair or replacement has been 
made. Install the new drier with the arrow on the drier in the direction of the 
refrigerant flow. 
4. When brazing, protect the drier by using a wet cloth to prevent the drier from 
overheating. Do not allow the drier to exceed 50°F (11°C).
5. Do not leave the system open for longer than 15 minutes when replacing or 
servicing parts.
1. Refrigerant Recovery
The icemaker is provided with refrigerant service valves. Using proper refrigerant practices, 
recover the refrigerant from the service valves and store it in an approved container. Do not 
discharge the refrigerant into the atmosphere.