Nortel Networks CVX 600 Manuel D’Utilisation

Page de 168
Mounting the CVX 600 in a Rack
1-8
296-1011-202 Rel. 5.0, Doc. Rev. 02.01 
CVX 600 Hardware Installation Guide
Properly ventilated
Well lighted 
Ceiling Requirements
Consider the following ceiling requirements before you install the rack:
The ceiling should be clear of obstructions such as beams, heating and air 
conditioning ducts, water pipes, and lights.
The ceiling should not have sprinklers; however, appropriate fire protection 
devices should be available.
Size and Weight Considerations
Before you install the rack at your site, make sure that the equipment room can 
accommodate the size and weight of the rack and the CVX 600.
To determine the total weight, add the weight of all of the CVX 600 chassis (about 
70 lb, 31.7 kg each for the AC chassis option, NTDZ10BA)
and the weight of the 
rack.
Reference
For information about general equipment requirements, see the Telcordia Network 
Equipment Building Standards (NEBS), General Equipment Requirements 
(GR-63).
Nortel Networks PTE 2000 Rack
Nortel Networks offers two types of PTE 2000 racks:
PTE 2000 NEBS-compliant rack (NTRU0134)
PTE 2000 ETSI-compliant rack (NTRU0234)
Note: 
The recommended aisle spacing is 29.5 in. (750 mm).