Emerson 200I/48-NT5C05C Manuel D’Utilisation

Page de 62
Installation   27 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
Procedure 6 - Connecting the ac male plug between the NT5C05CC rectifier 
and the ac female plug in a 1200 A cabinet 
Step Action 
Install the ac breaker ( 30 A / 3 phases per rectifier ) in the 380 / 
415 volts ac service panel. 
Put the ac breaker for the NT5C05CC rectifier, located in the ac 
service panel, to OFF. 
Run the metric no. 25 ( 10 AWG ) ac supply cable ( 3 conductors 
and ground ) to the female receptacle ( see Figure 8 ). Connect the 
female connector to the male connector. 
Run the signal cable from the rectifier to the interconnect board or 
controller as specified in the " Connecting the control signals " 
section. 
Secure the signal cables to the insulating busbar support, located in 
the cabinet, with cable ties. 
Start-up the rectifier as described in the “ Start-up “ section. 
end
 
Figure 8 - Connecting ac to the rectifier NT5C05CC 
GRD
TB1
L1 L2 L3
FEMALE CONNECTOR
SECT A-A
BROWN
BLUE
BLACK
GREEN/YELLOW
GREEN / YELLOW
BLACK
BROWN
R1 (TB1-L1)
BLUE
WIRE COLOR
CONNECTION
T3 (TB1-L3)
S2 (TB1-L2)
A
A