Functional description   37 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
VOLT / AMP digital meter switch 
This switch is used to select the measurement display mode of the digital 
meter. The output voltage or the output current modes can be selected. 
VOUT+, VOUT
−−−−
 test points 
These test points are used to measure the voltage at the point of regulation. 
A 5 kohm resistor is placed in series with both sensing leads to prevent 
short-circuits at the jack terminals. The resistor may affect reading 
accuracy, depending on the impedance of the meter. Refer to the 
Instruction Manual for your meter to determine its internal impedance and 
correction factor. 
4.2.6.  Float and equalize voltage control 
Local FLOAT / EQL switch and potentiometers 
The rectifier is equipped with a FLOAT / EQL switch. 
When the FLOAT / EQL switch is held in the EQL position, the rectifier 
goes into equalize mode and boosts the output voltage to the value set by 
the EQL potentiometer. 
When the switch FLOAT / EQL is held in the FLT position, the rectifier 
delivers a float voltage set by the FLT potentiometer. 
Remote equalize control EQL 
The rectifier is equipped with remote equalize control. This control is 
activated by a remote ground signal ( BAT RTN ). The rectifier returns to 
normal ( float voltage ) operation when this signal is removed. 
4.2.7.  Current limit adjustment and rectifier regulating test 
CL ADJ potentiometer 
The rectifier limits the output current to a select value ranging from 100 A 
to 210 A, set by the CL ADJ potentiometer. The factory adjustment is 
205 A ±5 A. Extended periods of operation in the current limiting mode 
and repeated transitions between constant-voltage operation and constant-
current operation have no detrimental effect on the performance or service 
life of the rectifier.