10.2.2.5  PI Controller Proportional and Integral terms 
The user can tune the performance of the PI controller to suit the process demands 
by adjusting P and I terms, P2280 and P2285. The demands of the process will 
determine the optimal type of response, from a rapid recovery response with 
overshoot to a damped response. By adjusting the P and I parameters it is possible 
to achieve different types of response. 
Example: 
The following figures show how different responses to a 5% PI setpoint step 
change on a pressure control system. The traces show the PI feedback signal, with 
1 V = 10%. The different responses are achieved by varying the settings of P2280 
and P2285. 
 
Figure 10-4  Quick response with overshoot: P2280 = 0.30; P2285 = 0.03 s 
 
Figure 10-5  Quick response with overshoot, but instability:P2280 = 0.55; P2285 = 0.03 s