Siemens 411 Manuel D’Utilisation

Page de 164
Issue 03/01 
10  Engineering Information 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
133
 
10.3.1 DC 
Braking 
In this method a controlled DC voltage is applied to the rotor. When using DC 
braking, the inverter output pulses are disabled and the actual time taken to bring 
the motor to a standstill cannot be predicted. Stored energy in the motor and the 
load is dissipated in the rotor therefore no regeneration occurs. 
The DC braking current is defined as a percentage of nominal motor current using 
parameter P1232. The current will be applied only when the motor is sufficiently 
demagnetized. If the demagnetization time for the motor (P0347), is reduced too 
much then the drive will trip on over current (F0001) when DC braking is activated. 
DC braking can be enabled by an external source such as a digital input. 
NOTE 
The braking time depends on the rampdown time as follows.  
 
 
 
 
 
Figure 10-14  DC Braking 
NOTE 
Frequent use of DC Braking can cause the motor to overheat.  
10.3.2 
Vdc Max Controller 
The MICROMASTER 411/COMBIMASTER 411 has a controller to limit the DC 
voltage (Vdc Max controller). When braking a load faster than would normally be 
possible, excess energy has to be dissipated. This energy is unable to go back into 
the input supply so the result is that the DC link voltage rises. If this voltage rises 
too high, the trip level will be reached and the output pulses disabled to prevent 
damage to the inverter. The Vdc Max controller automatically increases the 
frequency and extends the ramp down period so that the braking is not as fast, 
thus reducing the risk of an overvoltage trip and keeping the system running. This 
means that the system will ramp down on the voltage limit until a standstill or a new 
setpoint is reached. (Refer to Parameter P1240 for configuration details). 
Braking time = Rampdown-time  * 
P0305 (Motor rated current) 
r0207 (Inverter rated current)