2  Installation 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
33
 
2.5 Electrical 
Installation 
 
WARNING 
This equipment must be grounded.
 
♦ 
To ensure the safe operation of the equipment, it must be installed and 
commissioned by qualified personnel in full compliance with the warnings laid 
down in these operating instructions. 
♦ 
Take particular note of the general and regional installation and safety 
regulations regarding work on dangerous voltage installations (e.g. EN 
50178), as well as the relevant regulations regarding the correct use of tools 
and personal protective gear. 
♦ 
Never use high voltage insulation test equipment on cables connected to the 
inverter. 
♦ 
Power supply and motor terminals can carry dangerous voltages even if the 
inverter is inoperative; wait 5 minutes to allow the unit to discharge after 
switching off before carrying out any installation work. 
 
CAUTION 
The control and power supply cables must be laid separately. Do not feed them 
through the same cable conduit/trunking.
 
 
2.5.1 General 
 
WARNING 
The inverter must always be grounded
. If the inverter is not grounded correctly, 
extremely dangerous conditions may arise within the inverter which could prove 
potentially fatal. 
Operation with Residual Current Device 
If an RCD (also referred to as ELCB or RCCB) is fitted, the MICROMASTER 411 
Inverters will operate without nuisance tripping, provided that: 
 
A type B RCD is used. 
 
The trip limit of the RCD is 300 mA. 
 
The neutral of the supply is grounded. 
 
Only one inverter is supplied from each RCD. 
 
Operation with long cables 
All inverters will operate at full specification with cable lengths of 5 m.