2  Installation 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
39
 
2.5.5 Avoiding 
Electro-Magnetic Interference 
The inverters are designed to operate in an industrial environment where a high 
level of EMI can be expected. Usually, good installation practices will ensure safe 
and trouble-free operation. If you encounter problems, follow the guidelines stated 
below. 
Action to Take 
 
Make sure that any control equipment connected to the inverter (such as a 
PLC) is connected to the same ground or star point as the inverter via a short, 
thick link. 
 
Flat conductors are preferred as they have lower impedance at higher 
frequencies. 
 
Separate the control cables from the power connections as much as 
possible, using separate trunking, if necessary at 90
0
 right angles. 
 
Ensure that contactors are suppressed, either with R-C suppressors for AC 
contactors, or 'flywheel' diodes for DC contactors, fitted to the coils. Varistor 
suppressors are also effective. This is important when the contactors are 
controlled from the inverter relay. 
 
Screened motor cables should be used when the motor is mounted separately 
from the inverter. 
 
Maximum motor cable length is 5 meters (16.40 feet). 
 
 
WARNING 
Safety regulations must not be compromised when installing inverters!