4  Using the MICROMASTER 411 / COMBIMASTER 411 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
63
 
4.2 
 Command Sources (P0700) 
NOTICE 
The ramp times and ramp-smoothing functions also affect how the motor starts 
and stops. For details of these functions, please refer to parameters P1120, P1121, 
P1130 – P1134 in the Parameter List. 
Starting the motor 
 
Default 
Terminal 1 (DIN 1): (P0700=2) 
 
Other Settings 
see P0700 to P0704 
Stopping the motor 
There are several ways to stop the motor: 
 
Default: 
♦ 
OFF1 (4.3.1) 
Terminal 1 (DIN 1): (P0700=2) 
♦ 
OFF2 (4.3.2) 
Off button on BOP/AOP. Pressing the Off button once 
(two seconds) or twice (with default settings). This is not 
possible without BOP/AOP 
♦ 
OFF3 (4.3.3) 
no standard setting 
 
Other Settings  
see P0700 to P0704 
Reversing the motor 
 
Default 
 
Terminal 2 (DIN 2) 
 
Other Settings 
see P0700 to P0704 
 
 
4.3 
OFF and Braking Functions  
4.3.1 OFF1 
This command (produced by canceling the ON command) causes the inverter to 
come to a standstill at the selected ramp-down rate. 
Parameter to change ramp time see P1121 
NOTICE  
 
ON and the following OFF1 command must have the same source. 
 
If the ON/OFF1 Command is set to more than one Digital input, only the last 
set Digital Input is active e.g. DIN3 active. 
 
OFF1 can be combined with DC braking or Compound braking.