6  Troubleshooting 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
81
 
6.3 Faults 
and 
Alarms 
6.3.1 
Fault messages  
In the event of a failure, the inverter switches off and a fault code appears on the 
display. 
NOTE 
To reset the fault code, one of three methods listed below can be used: 
Method 1:   Cycle the power to the drive 
Method 2:   Press the 
 
 button on the BOP or AOP 
Method 3:   Via Digital Input 3 (Default Setting) 
 
Fault messages are stored in parameter r0947 under their code number (e.g. 
F0003 = 3). The associated error value is found in parameter r0949. The value 0 is 
entered if a fault has no error value. It is furthermore possible to read out the point 
in time that a fault occurred (r0948) and the number of fault messages (P0952) 
stored in Parameter r0947. 
F0001 OverCurrent 
OFF2 
Possible Causes 
 
Motor power (P0307) does not correspond to the inverter power (r0206) 
 
Motor leads are too long 
 
Motor lead short circuit 
 
Earth faults 
Diagnose & Remedy  
Check the following: 
 
Motor power (P0307) must correspond to inverter power (r0206) 
 
Cable length limits must not be exceeded 
 
Motor cable and motor must have no short-circuits or earth faults 
 
Motor parameters must match the motor in use 
 
Value of stator resistance (P0350) must be correct 
 
Motor must not be obstructed or overloaded 
 
Increase the ramp time 
 
Reduce the boost level (V/f control: P1311 & P1312, Vector control: P1610 & P1611) 
F0002 OverVoltage 
OFF2 
Possible Causes 
 
DC-link controller disabled (P1240 = 0) 
 
DC-link voltage (r0026) exceeds trip level (P2172) 
 
Overvoltage can be caused either by too high main supply voltage or if motor is in regenerative 
mode. Regenerative mode can be caused by fast ramp downs or if the motor is driven from an 
active load. 
Diagnose & Remedy  
Check the following: 
 
Supply voltage (P0210) must lie within limits indicated on rating plate 
 
DC-link voltage controller must be enabled (P1240) and parameterized properly 
 
Ramp-down time (P1121) must match inertia of load 
 
Required braking power must lie within specified limits 
NOTE 
Higher inertia requires longer ramp times; otherwise, apply braking resistor. 
F0003 UnderVoltage 
OFF2 
Possible Causes 
 
Main supply failed