Server Technology CDU CW-24VD Fascicule

Page de 2
Model
Available Input
 Voltages
Outlets
Available Input
 Cord
Amperage
Dimensions**
(L x W x D)
© Server Technology, Inc. 10/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-24VD/Y
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management 
with power distribution and power and environmental monitoring. 
Reboot a single or dual-power server with one command. Receive 
SNMP-based alerts and email alerts when power or environmental 
conditions exceed thresholds. Assign users specific access rights to 
designated outlets or groups. 
Only the Switched CDU products provide the flexibility needed for all 
data centers and remote sites, including power requirements for 
high-amp, high voltage; UL 60950-1 branch circuit protection; SSL & 
SSH security; and SNMP-based input current monitoring.
The Switched CDU also supports Enterprise View PDU Manager. 
This gives the engineer the ability to manage  a large installation of 
Networked CDUs from one location, view and access multiple Smart 
and Switched CDUs from a 
single web interface. 
> Remote Power Management: 
Power cycle individual power 
outlets, or groups of power 
outlets, to remotely reboot 
servers and network devices, 
anywhere in the world.  Or, 
power-off unused power 
receptacles
> High Power Distribution
3-Phase power; 20 or 30-Amp 
power input feed options 
> High Density:  Single power 
input feed; 24 outlets per 
enclosure
> IP Access & Security:  Web 
interface, SSL, SSH, Telnet, SNMP, 
FTP, SNTP, Syslog, LDAP, LDAPS, 
TACACS
 
and RS-232 access
> Add an Expansion Module:  
Daisy chain the Switched CDU 
Expansion Module (CW/CX) for 
power management of separate 
power circuits from a single IP 
address  
> Environmental Monitoring:  
Each Switched CDU supports two 
temperature & humidity probes 
and reports conditions thru the 
Web interface
> Enterprise View:  View and 
access multiple Switched CDUs 
from one Web interface**
> SNMP Traps: Provide automated 
alerts for power and 
environmental conditions
> Input Current Monitor: 
Precisely measure the aggregate 
current draw (in amps) on each 
power circuit.  On-site verification 
of the input current with the LED 
digital display.  Remote 
verification via browser or serial 
screen.
Power-up Sequencing: Prevent 
an in-rush power overload
 
Branch Circuit Protection
The Sentry CDU Family meets the new UL 60950-1 
requirement for branch circuit protection.  
Attention! 
The Sentry CDU products meet the above criteria by 
providing overcurrent protection with UL-listed Bussman SC fuses for  
each branch circuit. 
Input Current Monitoring 
The CDU’s exclusive True RMS current monitoring is critical 
to preventing overloads in high-density computing  
environments.  LED digital displays on the CDU enclosure 
report the input current of each phase or branch circuit.
              
Temperature and Humidity    
 
 
The Switched CDU supports two external probes. Each of 
these probes measure both temperature and humidity.  
Receive SNMP-based alert notifications when conditions 
exceed defined thresholds.
              
Additional Benefits:
CW-24V2-C20M
CW-24VY-L20M*
CW-24V2-L30M
CW-24VY-L30M*
208-240V
50/60Hz
208-240V
50/60Hz
3-Phase Wye, 208V
50/60Hz
3-Phase Wye, 208V
50/60Hz
30A
20A
30A
20A
IEC 60320/C20
Power Inlet
NEMA L6-30P
Cordset
NEMA L21-20P
Cordset
NEMA L21-30P
Cordset
(24) IEC 60320/C13*
(24) IEC 60320/C13*
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
Additional Features and Specifications
Branch Circuit Protection
> Compliant to UL 60950-1
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and               
   CAN/CSA 22.2 No. 60950-1-03 
        
> European Union (TUVGS mark) to EN 60950-1:2001  
> FCC Class A, Part 15 
    
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet 
        
> HTTP/HTTPS  
        
> SSLv3/TLSv1  
       
> SNMPv2   
 
        
> SSHv2
> Telnet
> LDAPv3
> LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
 
EMTH-1-1 Temperature & Humidity Probe, 10’
 
Power Cord Options
> PTCORD-1       IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2       IEC 60320/C19 - Schuko 10’ 
> PTCORD-3       IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 
                            16/20A Blue (UK Commando) 10’
> PTCORD-4       IEC 60320/C19 - BS1363 13A (UK) 10’
> PT-ADP-C19    Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module 
Model Numbers
> CX-24VD-L20M
> CX-24VD-L30M
> CX-24VY-L20M
> CX-24VY-L30M
(24) IEC 60320/C13
(24) IEC 60320/C13
CW-24VE-C20M
CW-24VE-P32M
230V
50/60Hz
230V
50/60Hz
32A
16A
IEC 60320/C20
Power Inlet
IEC 60309
Cordset
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
(24) IEC 60320/C13
(24) IEC 60320/C13
*This unit has an additional NEMA 5-20R, 110V Utility Outlet
**Please note that the depth of these enclosures are 3.0” deep at the placement of the fuse retractors
CW-24VD-L20M
CW-24VD-L30M
3-Phase Delta, 208V
50/60Hz
3-Phase Delta, 208V
50/60Hz
30A
20A
NEMA L15-20P
Cordset
NEMA L15-30P
Cordset
(24) IEC 60320/C13
(24) IEC 60320/C13
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
Ex
M