Multicarrier G2 Universal Module to R8r EPN
5-71
High Reliability
5
Set Additional Administration
1. Type list configuration software-version long and press
Enter
to
compare the version number of the DEFINITY ECS Release 8 software
program with the version number (written on a label on the processor’s
faceplate). If the version numbers are not the same, change the version
number on the processor label so that they agree.
program with the version number (written on a label on the processor’s
faceplate). If the version numbers are not the same, change the version
number on the processor label so that they agree.
2. Type change system-parameters customer-options and press
Enter
.
Use this screen to enable the Release 8 option and to assign the
customer’s other right-to-use options on the G2-to-DEFINITY ECS Release
8 upgrade order. See
customer’s other right-to-use options on the G2-to-DEFINITY ECS Release
8 upgrade order. See
DEFINITY Enterprise Communications Server
Release 8 Administrator’s Guide, for details on enabling these options.
3. Type change site-data and press
Enter
. Use this screen to assign
system-specific information (such as building, floor, stations, and so
forth).
forth).
4. Type status system 1 and press
Enter
to verify the system is in the
“active/standby” mode.
5. Type save translation and press
Enter
. This instructs the system to write all
translation information from memory to the translation card.
!
WARNING:
If the terminal screen displays “translation corruption detected; call
Lucent Technologies distributor immediately”, an error was detected
in the translations.
Lucent Technologies distributor immediately”, an error was detected
in the translations.
Reconnect Cables
1. At the power distribution unit of the upgraded EPN, set the main circuit
breaker to OFF.
NOTE:
Powering down an EPN without powering down the PPN will set off
alarms. However, these alarms should clear after power is restored
to each EPN.
alarms. However, these alarms should clear after power is restored
to each EPN.
2. Temporarily disconnect the lightwave transceivers and fiber optic cables,
already labeled, from the appropriate carriers.
3. Replace the back doors or back panels.
4. At the EPN cabinet, reconnect the lightwave transceivers, fiber optic
cables, and the connector cables associated with the carrier being
replaced.
replaced.
5. Install the front door on the EPN cabinet.