APC PTEL2R Fascicule

Page de 2
Model PNETR5 - In applications where the network data transmission rate is high and cable lengths are long, 
insertion loss introduced by in-line devices is a major consideration. At the 100 Mbp/s data transmission rate 
there is a small insertion loss introduced by the PNETR5. Use Table 1 below to approximate the insertion loss 
introduced by the PNETR5 based on your installed cable type. The ISO/IEC 8802-3 standard specifies a 
maximum UTP cable length of 150 meters per segment at 10 and 100 Mbp/s. For Thinnet, maximum cable 
length is 185 meters (607 ft.). 
Model PNETR6 - Applications where the network data transmission rate is high and cable lengths are long, 
an  insertion loss is introduced by in-line devices. At 250 Mbp/s there is a small insertion loss introduced by 
the PNETR6. Use Table 1 below to approximate the insertion loss based on the installed cable type. The ISO/
IEC 8802-3 standard specifies a 150 meter maximum UTP cable length per segment at 250 Mbp/s. 
Table 1 
Model PVR (Digital Cable Protection)
The PVR module provides digital cable protection for video/cable/modem equipment against surges and 
spikes caused by lightning and electrostatic discharge (ESD). It is compatible with cable television (CATV), a 
digital satellite system (DSS), television, video cassette recorder (VCR), cable modem and TV antenna 
equipment. It is also compatible with many DSS units that have operating voltages below 26 volts DC. The 
PVR is recognized by Underwriter’s Laboratories (UL
®
 ) as a secondary protector.
EIA/TIA 568 Category or 
Cable Type
Frequency
(MHz)
Attenuation
(db/100m)
Equivalent Cable 
Length (m)
3
10
9.8
1.0 (3.28 ft)
16
13.1
1.10 (3.5 ft)
16*
0.1*
1.0 (3.28 ft.)
4
10
7.2
1.4 (4.5 ft)
16
8.9
1.6 (5.2 ft)
5
10
6.6
1.5 (4.9 ft)
16
8.2
1.7 (5.6 ft)
5
100
22
12.5 (41 ft)
5e
100*
2.2*
10 (32.8 ft.) 
6
250*
5.8*
17.1 (56.1 ft.)
Note: Entries marked with an asterisk ( * ) are only valid for PNETR6. 
Item
Specification
EN 50083-4, Attenuation and Return Loss
<6 dB from 54-550 MHz and <8 dB 550-1002 MHz
Ingress Susceptance EIA 23
(-26) dBmV
Radiated Emissions
15 dBmV 360 degree
Frequency Range
1 MHz though 2.0 GHz
Insertion Loss
0 dB to 3.0 dB over rated frequency range
Agency Approvals
UL 497B, FCC 47 CFR 15, CLB-47 CFR Part 15 Subpart C
Module Information - Continued
Model P232R (RS232 Protection)
The P232R module is used for RS232 communications (RS232 multiports, asynchronous multiplexers, 
asynchronous printer spoolers) using unshielded, twisted-pair wiring with RJ-45 connectors. It protects up to 
four ports per unit. 
Model PDIGTR (Digital Telephone Protection)
The PDIGTR module is only designed to be used in T1, CSU, DSU, ISDN, DDS and Digital Leased Line 
telecommunication equipment, and TNV-1 or SELV circuits. Insertion loss introduced by in-line devices is a 
major consideration. 
I
f the device arrived damaged, notify the carrier immediately.
If the device requires service, do not return it to the dealer. The following steps should be taken:
1.
Go to http://www.apc.com/support/.
2.
Have the model number, serial number and date of purchase available. Be prepared to troubleshoot the 
problem with an APC Technical Support representative. If this is not successful, APC will issue a Return 
Merchandise Authorization (RMA) number and a shipping address.
Item
Specification
Lines Protected
Pins 1 - 8 on RJ-45 connector
Mode of Protection
Between send/receive pairs and any signal line to ground
Peak Voltage
± 2,000 Volts, 1.2/50 µs test waveform
Peak Current
150 Amps, 8/ 20 µs test waveform
Breakover (turn on) Voltage
19 Volts nominal between send/receive pairs
Response Time
<1 ns
Item
Specification
Lines Protected
Pins 1 - 8 on RJ-45 connector
Mode of Protection
Between send/receive pairs and any signal line to ground
Peak Voltage
± 2,000 Volts, 1.2/50 µs test waveform
Peak Current
100A (maximum with 10X 1000 µs waveform
Operating Current
150 mA  maximum
Breakover (turn on) Voltage
Metallic (line-to-line): 60Vdc nominal
Response Time
<1 ns
Regulatory Approval / Classification
UL 497A recognized, FCC
Module Information - Continued
Service
APC warrants its products to be free from defects in materials and workmanship under normal use and service 
for the lifetime of the original purchaser. Its obligation under this warranty is limited to repairing or replacing, 
at its sole option, any such defective products. To obtain service under warranty you must obtain a Returned 
Material Authorization (RMA) number from APC or an APC Service Center. Product must be returned to APC 
or an APC Service Center with transportation charges pre-paid and must be accompanied by a brief description 
of the problem and proof of date/place of purchase. This warranty applies only to the original purchaser. 
Limited Lifetime Warranty
Customer Service / Technical Support
For information please call the APC Customer Service Center at: 
American Power Conversion           1-401-789-5735 or 1-800-800-4APC (4272)
132 Fairgrounds Road                      http://www.apc.com/support or 
West Kingston, RI 01892 USA           esupport@apcc.com 
Federal Communications Commission (FCC) Notice
This equipment contains an FCC compliant RJ-45 modular jack. It is designed to be connected to the telephone 
network or premises wiring using compatible modular plugs and cabling, which comply with the requirements of 
FCC Part 68 rules. The Ringer Equivalence Number (REN) is used to determine the number of devices that may be 
connected to the telephone line. An excessive REN may cause the equipment to not ring in response to an incoming 
call. In most areas, the sum of the RENs of all equipment on a line should not exceed five (5).
In the unlikely event that this equipment causes harm to the telephone network, the telephone company can 
temporarily disconnect your service. The telephone company will try to warn you in advance of any such 
disconnection, but if advance notice isn’t practical, it may disconnect the service first and notify you as soon as 
possible afterwards. In the event such a disconnection is deemed necessary, you will be advised of your right to file 
a complaint with the FCC.
From time to time, the telephone company may make changes in its facilities, equipment, or operations that could 
affect the operation of connected equipment. If this occurs, the telephone company is required to provide you with 
advance notice so you can make the modifications necessary to maintain uninterrupted service. This product is not 
serviceable by the user.
Entire contents copyright 2006 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is 
prohibited. 
APC and the APC logo are registered trademarks of American Power Conversion Corporation. All other trademarks are the property of their respective 
owners. 
990-1383B  05/2006
Model PTEL2R (Analog Telephone Protection)
The PTEL2R module protects analog devices, including telephones, ADSL, ISDN2, voice mail, automated 
answering systems, fax machines and modems, from damage caused by lightning-generated electrical 
transients. Each PTEL2R module protects up to 2 lines.
Item
Specification
Lines Protected
Pins 3 & 4 / 5 & 6 on RJ-45 connector; accepts RJ-45/RJ-11 plugs
Mode of Protection
Metallic (Tip - Ring) and longitudinal (Tip + Ring - Ground)
Peak Voltage
± 2,000 Volts, 1.2/50 µs test waveform
Peak Current
150 Amps, 8/ 20 µs test waveform
Breakover (turn on) Voltage
270 Volts peak nominal between tip and ring
Overload Protection
Solid-state, self-resetting fuse
Response Time
<1 ns
Agency Approvals
UL 497A recognized
Warning:  Disconnect module wires before removing module. Do not put fingers or objects inside the chassis.