resetToDef
Access:
Administrator only
Description:
Reset all parameters to their default.
Example:
To reset all of the configuration changes except the TCP/IP settings for the Rack PDU, type:
resetToDef -p keepip
snmp, snmpv3
Access:
Administrator only
Description:
Enable or disable SNMP 1 or SNMP 3.
Example:
To enable SNMP version 1, type:
snmp -S enable
system
Access:
Administrator only
Description:
View and set the system name, the contact, the location and view up time as well as the
date and time, the logged-on user, and the high-level system status P, N, A (see “About the Main Screen”
on page 15 for more information about system status).
on page 15 for more information about system status).
Example 1:
To set the device location as
Test Lab
, type:
system -l “Test Lab”
Example 2:
To set the system name as
Don Adams
, type:
system -n “Don Adams”
Option
Arguments
Description
-p
all | keepip
Reset all configuration changes, including event actions, device settings, and,
optionally, TCP/IP configuration settings.
optionally, TCP/IP configuration settings.
Option
Arguments
Description
-S
enable | disable
Enable or display the respective version of SNMP, 1 or 3.
Option
Argument
Description
-n
<system name>
Define the device name, the name of the person responsible for the
device, and the physical location of the device.
device, and the physical location of the device.
Note:
If you define a value with more than one word, you must
enclose the value in quotation marks.
These values are also used by StruxureWare Data Center Expert and
the Rack PDU’s SNMP agent.
These values are also used by StruxureWare Data Center Expert and
the Rack PDU’s SNMP agent.
-c
<system contact>
-l
<system location>