APC AP8861 Manuel D’Utilisation

Page de 104
Metered Rack PDU User Guide
33
devNearOver
Access: 
Administrator, Device User
Description: 
Set or view the near-overload threshold in kilowatts for the device.
Example 1: 
To view the near-overload threshold, type:
apc> devNearOver
E000: Success
20.5 kW
Example 2: 
To set the near-overload threshold to 21.3 kW, type:
apc> devNearOver 21.3
E000: Success
devOverLoad
Access: 
Administrator, Device User
Description: 
Set or view the overload threshold in kilowatts for the device.
Example 1: 
To view the overload threshold, type:
apc> devOverLoad
E000: Success
25.0 kW
Example 2: 
To set the overload threshold to 25.5 kW, type:
apc> devOverLoad 25.5
E000: Success
Example 3:  
To view the overload threshold for guest Rack PDU 3, type:
apc> devOverLoad 3:
E000: Success
5.0 kW
devReading
Access: 
Administrator, Device User
Description: 
View the total power in kilowatts or total energy in kilowatt-hours for the device.
Example 1: 
To view the total power, type:
apc> devReading power
E000: Success
5.2 kW
Example 2: 
To view the total energy, type:
apc> devReading energy
E000: Success
200.1 kWh
Example 3:  
To view the total power for guest Rack PDU 3, type:
apc> devReading 3:power
E000: Success
4.2 kW
Argument
Definition
power
View the total power in kilowatts.
energy
View the total energy in kilowatt-hours.