APC AP8861 Manuel D’Utilisation
Metered Rack PDU User Guide
91
Verifying Upgrades and Updates
Verify the success or failure of the transfer
To verify whether a firmware upgrade succeeded, use the
xferStatus
command in the command line
interface to view the last transfer result, or use an SNMP GET to the
mfiletransferStatusLastTransferResult OID.
mfiletransferStatusLastTransferResult OID.
Last Transfer Result codes
Verify the version numbers of installed firmware.
Use the Web interface to verify the versions of the upgraded firmware modules by selecting the
Administration tab, General on the top menu bar, and About on the left navigation menu, or use an
SNMP GET to the MIB II sysDescr OID. In the command line interface, use the
about
command.
Code
Description
Successful
The file transfer was successful.
Result not available
There are no recorded file transfers.
Failure unknown
The last file transfer failed for an unknown reason.
Server inaccessible
The TFTP or FTP server could not be found on the network.
Server access denied
The TFTP or FTP server denied access.
File not found
The TFTP or FTP server could not locate the requested file.
File type unknown
The file was downloaded but the contents were not recognized.
File corrupt
The file was downloaded but at least one Cyclical Redundancy Check (CRC) failed.