Product Description
4
2.2
Operational Overview - Water/Glycol Cooled Model
The water/glycol cooled XDF model employs a single-stage cooling system rated at 14kW to supply 
cooling air to the rack-mounted equipment. A bank of fans circulates this cooling air through the elec-
tronic equipment in the XDF (see Figure 1).
An evaporator coil extracts heat from the circulating air. That heat is transferred to a brazed plate 
condenser at the top of the XDF, transferred to the cooling water or glycol solution and is piped out of 
the unit.
Coolant is piped through the back of the XDF through supply and return pipes with 1" female NPT 
connections (refer to Figure 2 or Figure 6).
The XDF’s backup ventilation system operates automatically if power fails or if any XDF cooling sys-
tem component fails.
If water is used as the coolant, Liebert recommends employing a closed system connected to an exter-
nal condensing unit. A closed water supply system protects the XDF from particles and other contam-
inants that might reduce cooling efficiency and damage the XDF.
Figure 2
Component location of water/glycol cooled model
Evaporator Fans
circulate cooling air
Rack-Mount 
Equipment 
Compartment 
(isolated from 
external air)
Compressor
Evaporator Coil
extracts heat from
air circulated 
through
the rack equipment
compartment
Coolant Return - in rear
Coolant Supply - in rear
Brazed Plate 
Condenser
(behind grille)
Front of XDF
iCOM Controller
Backup Ventilation 
Air Intake