Emerson 20002514 Manuel D’Utilisation

Page de 14
Step 2: Shield termination
Assemble the Gland
1. Fold the shield or braid back over the clamping insert and 1/8 inch 
(3 mm) past the O-ring.
2. Install the gland body into the conduit opening on the core processor housing.
3. Insert the wires through gland body and tighten the gland nut onto the gland body.
Apply the Heat Shrink
1. Slide the shielded heat shrink over the drain wires. Ensure that the 
wires are completely covered. 
2. Apply heat (250 °F or 120 °C) to shrink the tubing. Do not burn the 
cable.
3. Position the clamping insert so the interior end is flush with the braid 
of the heat shrink.
Cable shield 
type
Braided
(armored cable)
Foil
(shielded cable)
Go to Step 3
Terminate the shield 
and drain wires in the 
gland
Assemble the gland 
according to vendor 
instructions
Gland supplier
Micro Motion
cable gland
User-supplied
cable gland
From Step 1
After heat applied
Shield folded back
Gland body
Gland type
M20
Trim 7 mm from the shielded 
heat shrink
Shielded heat
shrink
Trim
NPT
Wiring
Installation Manual 
7