alarm WIrInG
Alarm relays can be wired for NO (close on alarm) or 
NC (open on alarm) strategy.
Alarm relays can be used individually if there are 
enough available building alarm points, or can be 
arranged into smaller groups or even a single group so 
that all alarm capabilities can be utilized.
When multiple alarms are grouped together and issued 
as a single alarm, there will no off-site indication of 
which specific problem may have occurred, only that 
one of the alarms in the group has been triggered.  The 
individual alarm problem will be shown on the LED 
display on the face of the controller.
Note: All alarm and output relays are Form C (SPDT) 
dry contacts rated 1A @ 24 VAC.
Note: All alarm relay outputs have 10-second delay in 
acutally issuing to protect against nuisance alarm signals.
The Power Loss 1, Power Loss 2 and controller alarm 
relays are all “reverse actuated”, which means they 
are continuously energized (the NO contact is closed) 
and switched to NC position upon alarm condition.  
Therefore, it is important to closely follow the alarm 
board connection diagrams that follow.
Any alarm feature that is not desired can simply be 
ignored (not connected).
NOtE: the LED display board can be replaced if 
needed independently of the alarm board.  Bard 
part number is 8612-022.
alarm leD DIsPlaY bOarD
MIS-2042
Note: The LED display board is polarized and will 
only fit in one direction as shown.  It must be fully 
inserted in order for the controller to function properly.
Note: the alarm LeD display board is shipped  
uninstalled to protect it from possible damage during  
installation of the wiring to main controller board and/
or the alarm board.  It is polarity sensitive and is keyed 
so it can only be installed in correct position.
ecOnOmIzer FaIlure alarm
Upon failure of either economizer to open on command 
or close on command, the Economizer Failure Alarm 
will open normally closed contacts to signal the 
failure.  To utilize this feature, terminals 8 & 9 must be 
connected to the shelter alarm panel.
A normally closed economizer fail alarm is available on 
terminals 8 & 9 of the Unit 1 & 2 terminal blocks.
DIrtY FIlter alarm
A normally closed dirty filter alarm is available on 
terminals 4 & 5 of the Unit 1 & 2 terminal blocks.
2-cOmPressOr run alarm
If both compressors are running at the same time, the 
2-Compressor Run Alarm will open indicating this 
condition.