Liebherr 7083 247-00 Manuel D’Utilisation

Page de 13
18
Adjusting the alarm parameters
The alarm limits (difference to the set temperature) and the alarm
delay (delay until alarm goes on) can be adjusted.
Press 
for 5 seconds. Display =
Display =
Display =
Display =
Display =
Display =
 
Display =
Lower alarm limit
Display = temperature difference in °C
Use buttons 
 and 
 to select the desired setting. 
Display =
Display =
  Upper alarm limit
Display = temperature difference in °C
Use buttons 
 and 
 to select the desired setting. 
Display =
Display =
 
Display = alarm delay in minutes
Use buttons 
 and 
 to select the desired setting. 
Display =
Press 
 for 5 seconds. 
The electronic control system will automatically switch back to 
normal operating mode.
Alarm messages
1. LED 
 
flashes
If 
 appears in the display, the appliance has a fault. Consult 
your nearest customer service point. 
2. LED 
 
flashes, the display reads 
HI
 or 
LO
The interior is too warm (HI) or too cold (LO).
The audible warning signal sounds (unless the audible warning 
signal function has been deactivated).
Note
The alarm parameters can be adjusted. See Adjusting the alarm 
parameters.
3. HACCP flashes
There has been a power cut of some length or the interior was too 
warm or too cold during a certain period of time.
Up to three alarm events can be stored and called up.
Alarm test
This test checks the function of the internal and any external 
connected alarm device.
The appliance does not stop its refrigerating function during this 
test.
Activating the test
Press 
 + 
 for 5 seconds. 
•  The display will change to a temperature value of 0.2°C below
the set upper alarm limit.
•  The temperature value will now rise by 0.1°C every 2 seconds.
•  When the upper alarm limit is reached, 
 will appear in the 
display. An external alarm unit connected to the floating alarm 
output will now be activated.
•  The temperature value will continue to rise up to 0.2°C above 
the upper alarm limit.
•  The same process will take place automatically for the lower 
alarm limit. 
 will appear in the display.
The LED
 will be lit during the test.
The electronic control system will automatically switch back to 
normal operating mode.
Cancelling the test prematurely
Press 
 for 5 seconds. 
Note
If the values of the upper and lower alarm limit (AL and AH in the 
section entitled "Adjusting the alarm parameters") are set to 0, 
 and 
 will appear in the display during this test.