MAINTENANCE SCHEDULES 
1.  6-MONTH MAINTENANCE (MUST BE PERFORMED BY AN   
 
AUTHORIZED ANSUL® DISTRIBUTOR ONLY)
 
     a. 
Inspect and test total operation including FIRE DAMPER and 
  all 
SAFETY 
INTERLOCKS. 
 
     b. 
All FIRE SUPPRESSION SYSTEM actuation components      
 
 
including MANUAL PULL STATION  and any REMOTE      
 
 
MANUAL PULL STATION must be inspected for proper         
 
 
operation in accordance with the maintenance schedule      
  published 
in 
ANSUL® R-102 SYSTEM DESIGN,  
 
 
 
 
INSTALLATION, RECHARGE AND MAINTENANCE MANUAL 
 
 
(Ansul® #418087-05). 
 
     c. 
The FIRE SUPPRESSION SYSTEM FUSIBLE LINKS must be 
 
 
inspected.  NOZZLES and MANUAL PULL STATION must be 
  cleaned 
in 
accordance 
with 
ANSUL® R-102 SYSTEM        
  DESIGN, 
INSTALLATION, 
RECHARGE AND MAINTENANCE  
  MANUAL 
(Ansul® #418087-05). 
 
     d. 
The FIRE SUPPRESSION AGENT TANK, PIPING and       
 
 
FLEXIBLE TUBING must be INSPECTED.  
 
2.  12-YEAR MAINTENANCE:  (MUST BE PERFORMED BY AN  
 
AUTHORIZED ANSUL® DISTRIBUTOR ONLY)
 
     a. 
The FIRE SUPPRESSION AGENT TANK and ¼” FLEX HOSE 
 
 
must be HYDROSTATICALLY TESTED, and the FIRE         
  EXTINGUISHING 
AGENT 
must 
be REPLACED in accordance 
 
 
with the maintenance schedule published in ANSUL® R-102  
 
 
SYSTEM (STANDARD UL 300 LISTED).  
     b. 
The FUSIBLE LINKS in plenum and damper must be                 
 
 
REPLACED.  This maintenance to be performed by qualified 
 
 
Ansul® service personnel only. 
USE AND MAINTENANCE 
SHALL BE IN ACCORDANCE 
WITH THE STANDARD FOR  
VENTILATION CONTROL 
AND FIRE PROTECTION OF 
COMMERCIAL COOKING   
OPERATIONS
, N.F.P.A 17A 
& N.F.P.A. 96 (current        
editions). 
 
DANGER 
 
Fire Hazard 
 
FAILURE TO PROPERLY 
CLEAN AND MAINTAIN THIS 
EQUIPMENT CAN 
CAUSE A FIRE.  AN          
UNCONTROLLED FIRE CAN 
CAUSE SERIOUS INJURY,  
DEATH AND/OR PROPERTY 
LOSS. 
 
 
NOTE:  A signed and dated 
VENTILATOR HOOD    
MAINTENANCE LOG must 
be maintained on the      
premises, and shall be    
available for inspection by the 
authority having jurisdiction. 
See pages 25 & 26. 
 
 
IMPORTANT:  Parts used 
for the Ansul® fire            
suppression system are not 
serviceable by  the owner / 
operator.  
Procedures for  
servicing fire suppression 
equipment are described in: 
ANSUL® R-102 SYSTEM  
DESIGN, INSTALLATION, 
RECHARGE AND          
MAINTENANCE  MANUAL 
(Ansul® #418087-05). 