SEQUENCE OF OPERATIONS
 
IMPINGER II ADVANTAGE 
MODEL 1116-000-A / NATURAL GAS / 120 VAC / 60 HZ / 1 PHASE 
MODEL 1117-000-A / L.P. GAS / 120 VAC / 60 HZ / 1 PHASE 
 
POWER SUPPLY 
Electrical power is supplied to the oven by a three conductor cordset.  Voltage 
from the black conductor to the white conductor is 120 VAC.  The white 
conductor is neutral.  The green conductor is ground. 
 
CONTROL BOX AUTO 
When the temperature in the control box reaches 120°F ± 3° (48.9°C ± 1.7°C), 
the  
COOL DOWN  
interrupt power to the fans when the control box temperature falls to 100°F ± 3° 
(37.8°C ± 1.7°C). 
 
MAIN FAN CIRCUIT 
Power is permanently supplied, through a 10A fuse, and through a normally 
closed control box hi-limit thermostat, to the normally open main fan switch.  
Power is also supplied to the normally open cooling fan thermostat.  Closing the 
main fan switch supplies 120 VAC to the main fan motor, the cooling fan motor, 
the primary of the temperature display transformer, the heat and conveyor 
circuits. 
 
BURNER CIRCUIT 
Closing the main fan switch supplies 120 VAC to the burner blower motor.  120 
VAC is also supplied, through the normally closed oven cavity hi-limit thermostat, 
the main fan centrifugal switch (this switch closes when main fan reaches 
approximately 1600 RPM) to the electronic temperature control and to the 
primary of the burner transformer. 
 
IGNITION CONTROL 
The ignition control operates on both 24 VAC and 120 VAC.  When the control is 
energized by 24 VAC from the transformer, 120 VAC is switched by the ignition 
control to the hot surface ignitor for 45 seconds for the hot surface ignitor warm 
up.  The ignitor glows red, 24 VAC is switched to the gas valve which opens and 
ignition should now occur. 
 
TEMPERATURE CONTROL 
When the centrifugal switch of the main fan motor closes, power is applied to the 
temperature control.  The 1K ohm temperature pot is adjusted to desired 
temperature.  The thermocouple will provide varying millivolts to the temperature 
controller.  The temperature controller supplies 120 VAC to the solenoid valve at 
intermittent intervals to maintain desired temperature.  The heat lamp is 
energized with the solenoid valve. 
 
CONVEYOR DRIVE 
Closing the on/off switch supplies 120 VAC to the motor control board.  AC volts 
are converted to DC volts and are supplied to the conveyor motor at terminals A+ 
and A-. 
 
 
Adjustment of the speed control potentiometer will change resistance at terminals 
P1 and P2 varying the DC voltage to the motor.  The speed of the conveyor 
motor will increase or decrease as the DC voltage from the board increases or 
decreases respectively. 
 
NOTE: 
The conveyor control uses a sensor and magnet, mounted on the conveyor 
motor that senses the motor speed.  Any change in motor load (±RPM) is 
detected by the sensor and the voltage to the motor is adjusted accordingly. 
 
Temperature Display 
Closing the switch supplies 120 VAC to the primary of the temperature display 
transformer.  The secondary of this transformer supplies 12 VAC to the temperature 
display.  The thermocouple supplies D.C. millivolts to the temperature display.  The 
display converts this millivolt reading to a temperature reading.