True Manufacturing Company GDM-26 Manuel D’Utilisation

Page de 9
ELSTAT SEQUENCE OF OPERATION
Once the cabinet is plugged in, the ELSTAT control will flash "888" and then 
go through a parameter check. Once completed, the control will do a "soft 
start". Lights come on first, approximately 30 seconds later the compressor 
will start. Approximately 30 seconds from the compressor start up, the evap 
motor will start. The control will display "Use".  The control will then cycle 
the compressor on and off at the predetermined temp (Model specific). 
The whole time the controller is on it is learning the customer traffic. Once 
enough data has been accumulated the controller will now cycle between 
two modes. "Standby" and "Use". In the standby mode the controller 
predicts that customer traffic is nonexistent. It will display (---). It cycles the 
compressor to hold about 50˚F. It shuts the lights off and cycles the evap 
fan motor. It will hold this pattern until roughly 2 hours before customer 
traffic is predicted to start. The controller will then switch into the "use" 
mode. Cycling the compressor on and off based on temperature (Approx 
36˚F to 38˚F product temp). Running lights continuously. The controller will 
then cycle between these two modes.
   3