Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
B-50
6 Changing Input Characteristics
6.1 Procedure for Changing Input Characteristics
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD/FX
3UC
-4AD (4-channel Analog Input)
6. Changing Input Characteristics
For the 4AD, the standard input characteristics are provided for each input mode (BFM #0) at the time of
factory shipment.
Changing the offset data (BFM #41 to #44) or gain data (BFM #51 to #54), however, can change the input
characteristics of each channel. This chapter describes how to change the input characteristics.
6.1
Procedure for Changing Input Characteristics
1
Determine the input mode (BFM #0)
Determine the optimum input mode (BFM #0) for the selected channels and the voltage/current
specifications.
Example: Enter "HFF00" in BFM #0 to set input mode 0 for channels 1 and 2 and prevent use channels 3 and
4.
Caution regarding data setting:
• If a channel is set to the value "2", "5", "8" or "F", the input characteristics of the channel cannot be 
changed.
• Set the optimum input mode for the analog signal to be input.
Set value 
(HEX)
Input mode
Analog input range
Digital output range
0
Voltage input mode
-10V to +10V
-32000 to +32000
1
Voltage input mode
-10V to +10V
-4000 to +4000
2
Voltage input analog value direct indication 
mode
The offset and the gain cannot be adjusted.
3
Current input mode
4mA to 20mA
0 to 16000
4
Current input mode
4mA to 20mA
0 to 4000
5
Current input analog value direct indication 
mode
The offset and the gain cannot be adjusted.
6
Current input mode
-20mA to +20mA
-16000 to +16000
7
Current input mode
-20mA to +20mA
-4000 to +4000
8
Current input analog value direct indication 
mode
The offset and the gain cannot be adjusted.
9 to E
Not used.
-
-
F
Channel not used
-
-